  Frequently Asked Questions

Frequently Asked Questions

Pipe Collars
Can pipe collars be used on metallic pipes?
What fixings do I need to install pipe collars?


Pipe Wraps
Are pipe wraps suitable for use on flexible constructions, such as plasterboard partitions?

PU Foam
I have used the Pyroplex fire rated foam to seal around cavity around a door, do I need treat the foam with any additional coatings to reinstate its fire resistance?.

Linear Gap Seals
We have installed the LGS system in a movement joint and positioned it centrally within the cavity is this sufficient?

Intumescent Acrylic and FR Silicone Sealants
In what application are these products suitable for?

Specialist Extrusions
We have identified a product within the specialist extrusions, which we would like to use, can minor modifications be made to the dimensions.

Intumescent Strip
What self-adhesive system is used on this type of product and will it stick to steel frames?

Air Transfer Grille System
Is the system suitable for ventilation ducts?

Glazing Systems
Is 300494 available in colours other than black?
Can the glazing system be used on timber screens?


Fire Door Seals -Rigid Box
How does the intumescent seal provide 30 minutes fire resistance?
Are your seals tested?
 

Pipe Collars

Can pipe collars be used on metallic pipes?

The melting temperature of such systems is in excess of the effective sealing range of the intumescent material. Pyroplex collars are for use on plastic flammable pipes. During a fire situation the plastic will start to soften, distort and slump, at this point the intumescent element will start to expand and fill the aperture and continue to expand until the cavity has been sealed.

What fixings do I need to install pipe collars?

Depending upon the type of the wall or floor construction we would recommend that the minimum fixing shall be M8 x 65 sleeve anchor or expanding bolt type. Do not rely upon fixings that rely upon plastic components for grip, this also applies to chemical fixings. 

Pipe Wraps

Are pipe wraps suitable for use on flexible constructions, such as plasterboard partitions?

Pipes passing through plasterboard type constructions are not necessarily fully lined and therefore will not offer the intumescent material a solid base to contain the expanding intumescent during a fire situation. In such cases Pyroplex recommends the use of its 400 series collars.

PU Foam

I have used the Pyroplex fire rated foam to seal around cavity around a door, do I need treat the foam with any additional coatings to reinstate its fire resistance?.

The system has been tested without any additional surface treatments to demonstrate its fire resistance performance. However, if the material is exposed to environmental conditions (such as ultra violet radiation) we would suggest that the material be capped with a mortar or other building material.

Linear Gap Seals

We have installed the LGS system in a movement joint and positioned it centrally within the cavity. Is this sufficient?

Depending upon the fire resistance classification the system will provide upto 2 hours fire resistance in this type of application. However, with the introduction of Approved Document L, it may be a requirement for the gap to be sealed for insulation purposes.

Intumescent Acrylic and FR Sealants

In what application are these products suitable for?

Intumescent Acrylic and Fire Rated Silicone can be used for sealing joints and gaps etc. Fire Rated Silicone can be used internally and externally, whereas intumescent acrylic can only be used internal. Both materials have different movement accommodations, see appropriate section for use and guidance.

Specialist Extrusions

We have identified a product within the specialist extrusions, which we would like to use, can minor modifications be made to the dimension?

The specialist range of extrusions is promoted in our literature to demonstrate our extrusion capabilities and diversity in terms of materials used. Some of the products displayed are for customer specific applications and therefore, no modifications can be made. We would recommend that you discuss your requirements directly with Pyroplex to enable us to produce an extrusion to meet your neeeds.

Intumescent Strip

What self-adhesive system is used on this type of product and will it stick to steel frames?

The self-adhesive tape used on this product range is a high performance self-adhesive backing for ease of application and installation. The system is a modified acrylic, with a double-sided system with a high coat weight of adhesive. Prior to the application of the product application the substrate must be cleaned to ensure that all oils, dust and other surface contaminates are removed. For specific information regarding the self-adhesive please contact Pyroplex technical.

Air Transfer Grille System

Is the system suitable for ventilation ducts?

At present we have no specific test evidence to demonstrate that the product is suitable for this particular application. The test evidence at present relates to timber doorsets for 30 and 60 minutes fire resistance. Our assessment report permits the use of this product in compartment walls for 30 and 60 minutes fire resistance.
 

Glazing Systems

Is 300494 available in colours other than black?

The product can be manufactured in other colours, such as brown, white, red, grey and cream subject to a minimum order quantity.

Can the glazing system be used on timber screens?

At present we have no primary test evidence to demonstrate its performance in terms of screens. However, recent tests conducted small-scale show no loss in performance when carried out at small scale using non-insulating glass, further tests are planned for 2006-2007.

Rigid Box Seals

How does the intumescent seal provide 30minutes fire resistance?

The active element of the system when heated >180°C starts to expand and continues to expand as the temperatures increases, effectively creating a fire stopping barrier to restrict hot gases and flame for the period of fire resistance.

Are you seals tested?

The Pyroplex range of seals have been tested to the requirements of BS476: Part 20/22:1987 for periods of 30 and 60 minutes fire resistance. Test reports are available upon request.